Function |
Specification |
|
Power input |
Input voltage(V) |
AC 3PH 200V~240V Rated voltage:220V AC 3PH 380V~480V Rated voltage:460V AC 3PH 520V~600V Rated voltage:575V |
Input frequency(Hz) |
50Hz or 60Hz, allowed range: 47~63Hz |
|
Power output |
Output voltage(V) |
0-input voltage |
Output frequency(Hz) |
Standard:0~400Hz;(380V Goodrive310 special inverters for medium-frequency:0~3200Hz) |
|
Technical control feature |
Control mode |
SVPWM, SVC |
Motor type |
Asynchronous and permanent magnet synchronous motors |
|
Speed ratio |
Asynchronous motor 1:200(SVC) synchronous motor 1:20(SVC) |
|
Speed control accuracy |
±0.2%(SVC) |
|
Speed fluctuation |
±0.3%(SVC) |
|
Torque response |
≤20ms(SVC) |
|
Starting torque |
Asynchronous motor: 0.5Hz/150%(SVC) Synchronous motor: 2.5Hz/150%(SVC) |
|
Overload capability |
G Type: 150% of rated current:1 minute P Type: 120% of rated current: 1 minute 180% of rated current:10 seconds 200% of rated current:1 second |
|
Running control feature |
Frequency setting method |
Digital setting, analog setting, pulse frequency setting, multi-step speed running setting, simple PLC setting, PID setting, MODBUS communication setting, PROFIBUS communication setting and CAN open communication setting. Switch between the combination and single setting channel. |
Auto- adjustment of the voltage |
Keep constant voltage automatically when the grid voltage transients |
|
Fault protection |
Provide more than 30 fault protection functions: overcurrent, overvoltage, undervoltage, overheating, phase loss and overload, etc. |
|
Peripheral interface |
Terminal analog input resolution |
≤20mV |
Terminal switch input resolution |
≤2ms |
|
Analog input |
1(AI1,AI2)0~10V/0~20mA and 1(AI3)-10~10V |
|
Analog output |
2(AO1, AO2)0~10V/0~20mA |
|
Digital input |
8 common inputs, the Max frequency: 1kHz; 1 high speed input, the Max frequency: 50kHz |
|
Digital output |
1 high speed pulse output, the Max frequency: 50kHz 1 Y terminal open collector output |
|
Relay output |
2 programmable relay outputs RO1A NO, RO1B NC, RO1C common terminal RO2A NO, RO2B NC, RO2C common terminal Contactor capacity: 3A/AC250V, 1A/DC30V |
|
Others |
Mountable method |
Wall and flange mountable |
Braking unit |
Built-in(≤30kW) External for others |
|
EMI Filter |
Built-in C3 filter: meet the degree requirement of IEC61800-3 C3, Optional external C2 filter: meet the degree requirement of IEC61800-3 C2 |
|
Temperature of the running environment |
-10~50℃, if above 40℃, derate 1% for every additional 1℃. |
|
Braking resistor |
Optional |
|
Protective degree |
IP20 |
|
Cooling |
Air-cooling |