  • CH series deceleration operation overcurrent OC2?

    1. Check the motor no-load current in the motor autotuning parameters is below 60% of the rated current, if the deviation is large, autotuning again.

    2. Check the inverter DEC time and whether the load rotation inertia is too large, whether there is a mutation in the load during the deceleration, or adjust PB protection parameter group. (CHF: decrease Pb.10=0,Pb.09; CHE: decrease  Pb.06, Pb.07; CHV: decrease Pb.11=1,Pb.12, set Pb.13 to be below 10Hz.

    3. If the problem persists, it may due to that the inverter model is too small, it is recommended to change to a inverter with larger power.

  • CH series acceleration operation overcurrent OC1?

    1. Determine whether to restart the motor in rotation, if yes, wait for the motor to stop and restart or set the speed tracking to be effective.

    2. Check whether the acc time of inverter is too short, and extend the acceleration time under the user's permission. If the customer process allows, the customer will be advised to replace the larger frequency converter.

    3. Make sure that the load of the inverter is changed in acceleration, and if yes, increase the protection value or extend the acceleration time.

    4. Check whether the output voltage is low at 50HZ, and adjust the motor no-load current to make the output voltage reach 380V.

    5. Check whether the output line is too long, and usually it is required to install output reactor or filter if exceeding 50m; Submersible pump generally must add reactor, otherwise OC1 will easily occur.
  • CH series motor autotuning fault TE?

    1. Check whether the motor has been connected before autotuning, and ensure the motor is connected correctly to the converter.

    2. Check whether the capacity of the motor matches with the inverter capacity. If the inverter capacity is too small, it is required to replace with the inverter which matches with the motor capacity.

    3. Check whether the rated motor parameters are set correctly, and ensure that the rated motor parameters are set correctly before autotuning.

    4. Check whether the parameters after inverter autotuning deviates from the actual values, if yes, carry out autotuning again until approximate parameters are obtained.

    5. See whether the setting of PE.02 is consistent with the inverter power, and correct those inconsistencies.
  • CH series inverter overload OL2?

    1. Determine whether to restart the motor in rotation. If yes, you can consider whether to start the motor or set the speed tracking to be effective after the motor is stopped.

    2. Check whether the ACC time of the inverter is too short, and extend the acceleration time under user's permission. For example, the customer process department allows the customer to replace with the inverter with larger power.

    3 Check whether the output voltage is low at 50HZ, and the output voltage of the motor can be adjusted to 380V.

    4. Check whether the current displayed by the keyboard is consistent with the actual current. If yes, it is recommended that the customer replace with the inverter of larger power.

    5. Check whether the inverter model is set correctly, (whether it corresponds to the load type, if not, reset the model).
  • CH series motor overload OL1?

    1 Check whether the rated parameters of the motor are correct. Please reset if incorrect.

    2 Check the frequency of the inverter is at 50HZ if the output voltage is 380V. If not, please adjust the motor no-load current to output at 380V.

    3 Check whether the motor protection parameter setting is correct. (CHF: Pb. 03; CHE: Pb. 01; CHV: Pb. 03), set protection parameters correctly.

    4 Check to see if the motor is blocked, if there is a traffic jam, try to eliminate it.

    5 Check the keyboard to show whether the current is the same as the actual measurement current. If it is consistent, it means the motor model is too small, and the customer is advised to replace with a motor with larger power.
  • Distractions?
    Inverter is a harmonic source which can interfere with controlequipment. Proper grounding is important, so the inverter should beindependently grounded, and the correct grounding can reduce the interferenceof the equipment by 60%.
  • Why it does not stop after pressing stop button and no fault trips?
    If the voltage is not high, the cause of failure may be: 1. Bad button of the inverter; 2. Press the stop button, the inverter slows down too fast and the load inertia is large, and there is no brake device; 3. Damage of main control board; 4. Deviation during autotuning is too large. 
  • How do you measure the main circuit?
    Usea digital meter with diode gear to measured R, S, T terminal rectifier bridgeswhich should be between 0.26-0.38. The voltage drop of U, V and W modulesshould be between 0.3-0.38 and balanced with each other. Then measure in areverse way and if the result is the same, it means the main circuit tubevoltage is normal.
  • The inverter jumps OC1, OC3 at power up?
    Ifthe inverter does not drive the motor, the cause of the failure could be: 1.The current detection circuit is damaged; 2. Hall burnt out; 3. Poor controlboard.
  • No display at power up?
    Ifthe power indicator light is on, the possible reasons for why the keyboard doesnot display the fault: 1. Drive power plate is damaged or short circuited; 2.Bad keyboard contact or burnt keyboard; 3. Damage of main control board; 4.Keyboard display setting error. If the power indicator is not on, the cause offailure may be: 1. There is no power input; 2. The fuse is broken; 3. Therectifying bridge is broken.
  • Why is terminal function invalid?
    Possiblecauses of failure: 1. Loss of the terminal 24V and PW bronze medal; 2. Terminal24V voltage is abnormal; 3. Terminal damage; 4. Error of terminal polaritysetting; 5. Improper parameter setting.

  • The inverter displays POFF at power up for operation?
    Possiblecauses of failure: 1. The input voltage is too low; 2. Failure of phase plate;3. Failure of master control board; 4. Voltage setting error 
  • What is the maintenance address and contact number for INVT inverters?
    Now we have 3 maintenance centers, so you can select the proper repair center to repair the machine. 
    1. Wuxi maintenance center address: room 601, no.2 building, Xinzhou business science park, no. 89, xingchuang road, Wuxi new district, Tel: 18002568725, 13771142233; contact: Shen jian, Ju ping 
    2. Shenzhen maintenance center address: Shenzhen INVT Electric Co., Ltd., Fuyong street, Baoan district, Shenzhen city. Contact: 0755-86312864, 0755-86312902; contact: Cheng ping, Long guo qiang 
    3. Shenyang maintenance center address: room 1502, no. 48-1, Guanfang garden, no. 48-1, cultural road, Heping district, Shenyang, Liaoning province, tel. 18002568737 024-31502457; contact: Lin tian yi 

  • What is the after-sale maintenance period of INVT inverters?
     At present, our company has establishedmaintenance centers in Chengdu, Taizhou, Baoding, Jinan, Wuxi, Shenyang and Shenzhento ensure that customers across the country can enjoy all around after-saleservice. We will complete the full process of maintenance within 2 days uponreceiving the inverters.
目前在第5页, 共有6页, 共有76条记录 第一页 上一页 23456 下一页 最后一页 跳转到
Email: overseas@invt.com.cn
Learn more about latest solutions and cases, please enter your email address to subscribe to
Online top

Our site uses cookies to provide you with a better onsite experience. By continuing to browse the site you are agreeing to our use of cookies in accordance with our Cookie Policy .