For GD300-21, what parameters need to be set when the air compressor is powered on for the first time?
2022-08-16
A

After logging in on the touch screen,
1. "Menu"-"Main Inverter Parameters"-"Fan Inverter Parameters" to set the parameters of the main motor and fan;
2. "System Configuration"-"Motor Parameter Setting"-"System Parameter Setting"-"Debug Mode" to complete the system configuration;
3. Set "User Parameters" and "Protection Parameters".
After ensuring that the air compressor is installed and connected correctly, you can start a trial run.

Q
What type of temperature sensor does GD300-21 support? How many temperature inputs are there?
2022-08-16
A

GD300-21 supports PT100 temperature sensor with two inputs.

Q
What is the input power factor of GD300-21?
2022-08-16
A

All GD300-21 series are equipped with built-in DC reactor as standard, and the power factor can reach above 0.9.

Q
What's the meaning of circulating variable frequency pump?
2022-08-16
A

The circulating variable frequency pump is one of the working modes of the GD300-16 HVAC special mode. In the long-term stable operation of the water supply system, the variable frequency pump has been running for a long time, which will affect its service life, and other variable frequency pumps are not involved in operation. In order to prolong the service life of the variable frequency motor, under the stable state of the system, all the variable frequency motors to be started run in turn according to the set cycle.
First, the inverter coast stop, and then controls the lower limit frequency of the cyclic variable frequency motor to be started as the initial set frequency, and superimposes PID1 to adjust the output frequency on the basis of this frequency as the final set frequency to start running, and finish the cycle process.

Q
Once the frequency exceeds 31hz, the output current surges, resulting in overcurrent and overload fault
2022-08-16
A

Gd200a drives 380V 50Hz motor.
When the 380V 50Hz motor runs to 31hz, the corresponding output voltage is 236v. If the current surges beyond this voltage, it can be judged that the motor is 220V. Use 220V inverter or change the motor winding connection method.

Q
When the large inertia load stops, the inverter has stopped, but the load motor is still rotating
2022-08-16
A

(such as the drum of industrial washing machine)
Set magnetic flux braking and DC braking; Cancel overvoltage stall and AVR function; If still can't stop the load, need to install the braking resistor;

Q
How to solve the problem of power grid fluctuation with resistive load?
2022-08-16
A

In V/F mode, please adjust P04.09 = 0, P08.41 = 00; check under-voltage point of factory parameter.
In vector mode, please adjust P03.04 = 2.5, P08.41 = 00. check under-voltage point of factory parameter.

Q
How to solve the OV problem of large inertia load?
2022-08-16
A

In V/F mode, please adjust P04.09 = 0, P08.41 = 00;
In vector mode, please adjust P03.04 = 2.5, P08.41 = 00.

Q
How to do PID adjustment?
2022-08-15
A

First check proportional, then integral, and finally add differential
The curve oscillates frequently, and the scale dial should be enlarged
The curve floats around the big bay, and the scale dial pulls to the small
The curve deviates and recovers slowly, and the integration time decreases
The curve has a long fluctuation period and the integration time is longer
The oscillation frequency of the curve is fast. First reduce the differential
It fluctuates slowly when the dynamic difference is large, the differential time should be longer.